A-20 Specifications

Table A.24 1762-IT4 Repeatability at 25°C (77°F)

(1)

(2)

(1) Repeatability is the ability of the input module to register the same reading in successive measurements for the

same input signal.

(2) Repeatability at any other temperature in the 0 to 60°C (32 to 140°F) range is the same as long as the

temperature is stable.

Input Type

Repeatability for
10 Hz Filter

Thermocouple J

±0.1 °C [±0.18 °F]

Thermocouple N (-110…1300 °C [-166…2372 °F])

±0.1 °C [±0.18 °F]

Thermocouple N (-210…110 °C [-346…166 °F])

±0.25 °C [±0.45 °F]

Thermocouple T (-170…400 °C [-274…752 °F])

±0.1 °C [±0.18 °F]

Thermocouple T (-270…170 °C [-454…274 °F])

±1.5 °C [±2.7 °F]

Thermocouple K (-270…1370 °C [-454…2498 °F])

±0.1 °C [±0.18 °F]

Thermocouple K (-270…170 °C [-454…274 °F])

±2.0 °C [±3.6 °F]

Thermocouple E (-220…1000 °C [-364…1832 °F])

±0.1 °C [±0.18 °F]

Thermocouple E (-270…220 °C [-454…364 °F])

±1.0 °C [±1.8 °F]

Thermocouples S and R

±0.4 °C [±0.72 °F]

Thermocouple C

±0.2 °C [±0.36 °F]

Thermocouple B

±0.7 °C [±1.26 °F]

±50 mV

±6

μ

V

±100 mV

±6

μ

V