Dh-485 communication protocol, Devices that use the dh-485 network – Rockwell Automation 1762-Lxxxx MicroLogix 1200 Programmable Controllers User Manual

Page 135

Advertising
background image

Publication 1762-UM001G-EN-P - March 2011

Connect to Networks via RS-232 Interface E-5

DH-485 Communication
Protocol

The DH-485 protocol defines the communication between multiple devices
that coexist on a single pair of wires. DH-485 protocol uses RS-485
Half-duplex as its physical interface. (RS-485 is a definition of electrical
characteristics; it is not a protocol.) RS-485 uses devices that are capable of
co-existing on a common data circuit, thus allowing data to be easily shared
between devices.

The DH-485 protocol supports two classes of devices: initiators and
responders. All initiators on the network get a chance to initiate message
transfers. To determine which initiator has the right to transmit, a token
passing algorithm is used.

Devices that use the DH-485 Network

In addition to the MicroLogix 1200 controllers, the devices shown in the
following table also support the DH-485 network.

Table E.1 Allen-Bradley Devices that Support DH-485 Communication

Catalog
Number

Description

Installation Function

Publication

Bulletin 1761
Controllers

MicroLogix 1000

Series C or
higher

These controllers support DH-485 communications.

1761-6.3

Bulletin 1764

MicroLogix 1500

Series A or
higher

These controllers support DH-485 communications.

1764-UM001

Bulletin 1747
Processors

SLC 500
Processors

SLC Chassis These processors support a variety of I/O requirements and

functionality.

1747-UM011

1746-BAS

BASIC Module

SLC Chassis Provides an interface for SLC 500 devices to foreign devices.

Program in BASIC to interface the 3 channels (2 RS232 and 1
DH-485) to printers, modems, or the DH-485 network for data
collection.

1746-UM004
1746-PM001
1746-RM001

1785-KA5

DH

+

/DH-485

Gateway

(1771) PLC
Chassis

Provides communication between stations on the PLC-5 (DH+)
and SLC 500 (DH-485) networks. Enables communication and
data transfer from PLC to SLC 500 on DH-485 network. Also
enables programming software programming or data acquisition
across DH+ to DH-485.

1785-6.5.5
1785-1.21

2760-RB

Flexible Interface
Module

(1771) PLC
Chassis

Provides an interface for SLC 500 (using protocol cartridge
2760-SFC3) to other A-B PLCs and devices. Three configurable
channels are available to interface with Bar Code, Vision, RF,
Dataliner, and PLC systems.

1747-6.12
2760-ND001

1784-KTX,
-KTXD

PC DH-485 IM

IBM XT/AT
Computer
Bus

Provides DH-485 using RSLinx.

1784-6.5.22

1784-PCMK

PCMCIA IM

PCMCIA slot
in computer
and
Interchange

Provides DH-485 using RSLinx.

1784-6.5.19

1747-PT1

Hand-Held
Terminal

NA

Provides hand-held programming, monitoring, configuring, and
troubleshooting capabilities for SLC 500 processors.

1747-NP002