F-2 System Loading and Heat Dissipation

Validate the System

The example systems shown in the tables below are verified to be acceptable
configurations. The systems are valid because:

Calculated Current Values < Maximum Allowable Current Values

Calculated System Loading < Maximum Allowable System Loading

Table F.2 Calculating the Current for Expansion I/O

Catalog Number

(1)

n

A

B

n x A

n x B

Number of
Modules

Device Current Requirements
(max)

Calculated Current

at 5V dc (mA)

at 24V dc (mA)

at 5V dc (mA)

at 24V dc (mA)

1762-IA8

2

50

0

100

0

1762-IF4

40

50

1762-IF2OF2

40

105

1762-IQ8

50

0

1762-IQ16

70

(2)

0

1762-IQ32T

170

0

1762-IR4

40

50

1762-IT4

40

50

1762-OA8

115

0

1762-OB8

115

0

1762-OB16

175

0

1762-OB32T

175

0

1762-OF4

40

165

1762-OV32T

175

0

1762-OW8

2

80

90

160

180

1762-OW16

140

(2)

180

(2)

1762-OX6I

110

110

1762-IQ8OW6

110

80

Total Modules (6 maximum):

4

Subtotal 2:

260

180

(1) Refer to your expansion I/O Installation Instructions for Current Requirements not listed in this table.