Publication 1762-UM001G-EN-P - March 2011

Specifications A-19

Table A.23 Input Specifications 1762-IT4

Specification

Value

Heat dissipation

1.5 Total Watts (The Watts per point, plus the
minimum Watts, with all points energized.)

Response speed per channel

Input filter and configuration dependent.

Rated working voltage

(1)

(1) Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including

the input signal and the value that floats above ground potential (for example, 30V dc input signal and 20V dc
potential above ground).

30V ac/30V dc

Normal mode rejection ratio

85 dB (minimum) at 50 Hz (with 10 Hz or 50 Hz filter)
85 dB (minimum) at 60 Hz (with 10 Hz or 60 Hz filter)

Maximum cable impedance

25

Ω (

for specified accuracy)

Open-circuit detection time

7 ms to 1.515 seconds

(2)

(2) Open-circuit detection time is equal to the module scan time, which is based on the number of enabled

channels, the filter frequency of each channel, and whether cyclic calibration is enabled.

Calibration

The module performs autocalibration upon power-up
and whenever a channel is enabled. You can also
program the module to calibrate every five minutes.

CJC accuracy

±1.3 °C (±2.34 °F)

Maximum overload at input
terminals

±35V dc continuous

(3)

(3) Maximum current input is limited due to input impedance.

Input channel configuration

via configuration software screen or the user program
(by writing a unique bit pattern into the module’s
configuration file).