Rockwell Automation 1762-Lxxxx MicroLogix 1200 Programmable Controllers User Manual

Page 117

Advertising
background image

Publication 1762-UM001G-EN-P - March 2011

Specifications A-25

Vendor ID code

1

Product type code

7

Product code

98

Table A.32 DC-Input/Relay-Output Combination Module - 1762-IQ80W6
Environmental Specifications

Specification

Value

Temperature range, operating

-20…+65 °C (-4…+149 °F)

Temperature range, storage

-40…+85 °C (-40…+185 °F)

Operating humidity

5…95% non-condensing

Operating altitude

2000 m (6561 ft)

Table A.33 Certifications

Certification

Value

Agency certification

C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives

Hazardous environment class

Class I, Division 2, Hazardous Location,
Groups A, B, C, D (UL 1604, C-UL under
CSA C22.2 No. 213)

Radiated and conducted emissions

EN50081-2 Class A

Electrical/EMC:

The module has passed testing at the
following levels:

ESD immunity (IEC1000-4-2)

4 kV contact, 8 kV air, 4 kV indirect

Radiated RF immunity
(IEC1000-4-3)

10 V/m, 80…1000 MHz, 80% amplitude
modulation, +900 MHz keyed carrier

EFT/B immunity (IEC1000-4-4)

2 kV, 5 kHz

Surge transient immunity
(IEC1000-4-5)

2 kV common mode, 1 kV differential
mode

Conducted RF immunity
(IEC1000-4-6)

10V, 0.15…80 MHz

(1)

(1) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency

range is 30…1000 MHz.

Table A.31 DC-Input/Relay-Output Combination Module - 1762-IQ80W6 General