Publication 1762-UM001G-EN-P - March 2011

System Loading and Heat Dissipation F-7

Validate the System

The example systems shown in Table F.11 and Table F.12 are verified to be
acceptable configurations. The systems are valid because:

Calculated Current Values < Maximum Allowable Current Values

Calculated System Loading < Maximum Allowable System Loading

Table F.11 Validating Systems using 1762-L40AWA, 1762-L40BXB, 1762-L40AWAR or 1762-L40BXBR

Maximum Allowable Values

Calculated Values

Current:

Current (Subtotal 1 from Table F.9 + Subtotal 2 from Table F.10):

600 mA at 5V dc

500 mA at 24V dc

0 mA + 435 mA = 435 mA at 5V dc

120 mA + 285 mA = 405 mA at 24V dc

System Loading:

System Loading:

15 Watts

= (4.5 mA x 5V) + (405 mA x 24V)
= (2175 mW) + (9720 mW)
= 11,895 mW
= 11.90 Watts

Table F.12 Validating Systems using 1762-L40BWA or 1762-L40BWAR

Maximum Allowable Values

Calculated Values

Current for Devices Connected to the +24V dc
Sensor Supply:

Sum of all current sensors

400 mA at 24V dc

150 mA at 24V dc (example sensor value)

Current for MicroLogix Accessories and
Expansion I/O:

Current (Subtotal 1 from Table F.9 + Subtotal 2 from Table F.10):

600 mA at 5V dc

500 mA at 24V dc

0 mA + 435 mA = 435 mA at 5V dc

120 mA + 285 mA = 405 mA at 24V dc

System Loading:

System Loading:

16 Watts

= (150 mA x 24V) + (435 mA x 5V) + (405 mA x 24V)

= (3600 mW) + (2175 mW) + (9720 mW)

= 15,495 W

= 15.50 Watts