Critical and noncritical errors, Module error definition table – Rockwell Automation 1762-Lxxxx MicroLogix 1200 Programmable Controllers User Manual

Page 125

Advertising
background image

Publication 1762-UM001G-EN-P - March 2011

Troubleshoot Your System C-5

Critical and Noncritical Errors

Noncritical module errors are recoverable. Channel errors (over-range or
under-range errors) are noncritical. Noncritical error conditions are indicated
in the module input data table. Noncritical configuration errors are indicated
by the extended error code.

See Table C.5 on page C-7.

Critical module errors are conditions that prevent normal or recoverable
operation of the system. When these types of errors occur, the system leaves
the run mode of operation.

Critical module errors are indicated in Table C.5 on page C-7.

Module Error Definition Table

Analog module errors are expressed in two fields as four-digit Hex format
with the most significant digit as ‘don’t care’ and irrelevant. The two fields are
‘Module Error’ and ‘Extended Error Information’. The structure of the
module error data is shown below.

Table C.3 Module Error Table

‘Don’t Care’ Bits

Module Error

Extended Error Information

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Hex Digit 4

Hex Digit 3

Hex Digit 2

Hex Digit 1

Advertising
This manual is related to the following products: