Rockwell Automation 1762-Lxxxx MicroLogix 1200 Programmable Controllers User Manual

Page 97

Advertising
background image

Publication 1762-UM001G-EN-P - March 2011

Specifications A-5

Surge current per point:

peak current

maximum surge duration

maximum rate of repetition at 30 °C (86 °F)

maximum rate of repetition at 55 °C (131 °F)

4.0A

10 ms

once every second

once every 2 seconds

Not applicable

Not applicable

Not applicable

Not applicable

Turn-on time, max.

0.1 ms

6 µs

Turn-off time, max.

1.0 ms

18 µs

Repeatability, max.

n/a

2 µs

Drift, max.

n/a

1 µs per 5 °C (41 °F)

(1) Output 2 is designed to provide increased functionality over the other FET outputs. Output 2 may be used like the other FET transistor outputs, but in addition, within a

limited current range, it may be operated at a higher speed. Output 2 also provides a pulse train output (PTO) or pulse width modulation output (PWM) function.

Table A.4 BXB FET Output Specifications

Attribute

General Operation

High Speed Operation

(1)

(Output 2 Only)

Table A.5 AC Input Filter Settings

Nominal Filter Setting (ms)

ON Delay (ms)

OFF Delay (ms)

Minimum Maximum

Minimum Maximum

8 2

20

10

20

Table A.6 Fast DC Input Filter Settings (Inputs 0 to 3)

Nominal Filter Setting (ms)

ON Delay (ms)

OFF Delay (ms)

Maximum Counter Frequency (Hz)
50% Duty Cycle

Minimum Maximum

Minimum Maximum

0.025

0.005

0.025

0.005

0.025

20.0 kHz

0.075

0.040

0.075

0.045

0.075

6.7 kHz

0.100

0.050

0.100

0.060

0.100

5.0 kHz

0.250

0.170

0.250

0.210

0.250

2.0 kHz

0.500

0.370

0.500

0.330

0.500

1.0 kHz

1.00

0.700

1.000

0.800

1.000

0.5 kHz

2.000

1.700

2.000

1.600

2.000

250 Hz

4.000

3.400

4.000

3.600

4.000

125 Hz

8.000

(1)

6.700

8.000

7.300

8.000

63 Hz

16.000

14.000

16.000

14.000

16.000

31 Hz

(1) This is the default setting.

Advertising
This manual is related to the following products: