Publication 1762-UM001G-EN-P - March 2011

Wire Your Controller 3-29

Figure 3.37 1762-IF4 Terminal Block Layout

Figure 3.38 Differential Sensor Transmitter Types

TIP

Grounding the cable shield at the module end only
usually provides sufficient noise immunity.
However, for best cable shield performance, earth
ground the shield at both ends, using a 0.01µF
capacitor at one end to block AC power ground
currents, if necessary.

IN 1 (+)

IN 0 (+)

IN 1 (-)

IN 0 (-)

IN 3 (+)

IN 2 (+)

IN 3 (-)

IN 2 (-)

COM

COM

Commons internally connected.

IN 0 (+)

IN 0 (-)

IN 3 (+)

IN 3 (-)

IN 2 (+)

IN 2 (-)

COM

IN 1 (-)

IN 1 (+)

COM

Analog Sensor