4-2 Communication Connections

The 1762-L24AWAR, 1762-L24BWAR, 1762-L24BXBR, 1762-L40AWAR,
1762-L40BWAR, and 1762-L40BXBR controllers are equipped with an
additional RS-232 communication channel called the Programmer/HMI Port,
which supports DH Full-duplex only. The controller cannot initiate messages
through this port. It can only respond to messages sent to it. All
communication parameters are fixed and cannot be changed by a user.

See Default Communication Configuration on page 4-2 for the configuration
settings.

For more information on MicroLogix 1200 communications, refer to the
MicroLogix 1200 and MicroLogix 1500 Programmable Controllers Instruction
Set Reference Manual, publication number 1762-RM001.

Default Communication
Configuration

The MicroLogix 1200 has the following default communication configuration.
The same default configuration is applied for both Channel 0 and the
Programmer/HMI Port (for 1762-LxxxxxR only). The configurations for the
Programmer/HMI Port are fixed and you cannot change them.

See Appendix E for more information about communicating.

TIP

For Channel 0, the default configuration is present
when:

The controller is powered-up for the first time.

The communications toggle push button specifies
default communications (the DCOMM LED is on).

An OS upgrade is completed.

Table 4.1 DF1 Full-duplex Default Configuration Parameters

Parameter

Default

Baud Rate

19.2K

Parity

none

Source ID (Node Address)

1

Control Line

no handshaking

Stop Bits

1