Wire Your Controller 3-25

Figure 3.33 1762-IQ8OW6 Wiring Diagram

Analog Wiring

System Wiring Guidelines

Consider the following when wiring your analog modules:

The analog common (COM) is not connected to earth ground inside the
module. All terminals are electrically isolated from the system.

Channels are not isolated from each other.

Use Belden 8761, or equivalent, shielded wire.

Under normal conditions, the drain wire (shield) should be connected to
the metal mounting panel (earth ground). Keep the shield connection to
earth ground as short as possible.

To ensure optimum accuracy for voltage type inputs, limit overall cable
impedance by keeping all analog cables as short as possible. Locate the
I/O system as close to your voltage type sensors or actuators as
possible.

The module does not provide loop power for analog inputs. Use a
power supply that matches the input transmitter specifications.