Publication 1762-UM001G-EN-P - March 2011

Specifications A-13

Isolated groups

Group 1: Outputs 0…15

Group 2: Outputs 16…31
(internally connected to
common)

Group 1: Outputs 0 to 3
Group 2: Outputs 4 to 7

Group 1: Outputs 0 to 7
Group 2: Outputs 8 to 15

All 6 Outputs Individually
Isolated.

Output group to
backplane isolation

Verified by one of the
following dielectric tests:
1200V ac for 2 s or 1697V
dc for 2 s.

75V dc working voltage
(IEC Class 2 reinforced
insulation)

Verified by one of the following dielectric tests: 1836V ac for 1 s or 2596V dc for
1 s.

265V ac working voltage (IEC Class 2 reinforced insulation)

Output group to output
group isolation

Verified by one of the
following dielectric tests:
1200V ac for 2 s or 1697V
dc for 2 s.

75V dc working voltage
(IEC Class 2 reinforced
insulation)

Verified by one of the following dielectric tests: 1836V ac for 1 s or 2596V dc for
1 s.

265V ac working voltage (basic insulation)
150V ac working voltage (IEC Class 2 reinforced insulation)

Vendor I.D. code

1

Product type code

7

Product code

102

120

121

124

(1) Only applicable to Series B I/O modules.

Table A.15 Output Specifications

Specification

1762-OV32T

1762-OW8

1762-OW16

1762-OX6I

Table A.16 Relay Contact Ratings (1762-OW8 and 1762-OW16)

Maximum Volts Amperes

Amperes
Continuous

Volt-Amperes

Make

Break

Make

Break

240V ac

7.5 A

0.75 A

2.5 A

(2)

(2) 1.5 A above 40 °C (104 °F).

1800VA

180VA

120V ac

15 A

1.5 A

2.5 A

(1)

1800VA

180VA

125V dc

0.22 A

(1)

(1) For dc voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28

VA by the applied dc voltage. For example, 28VA/48V dc = 0.58 A. For dc voltage applications less than 14 V, the
make/break ratings for relay contacts cannot exceed 2 A.

1.0 A

28VA

24V dc

1.2 A

(2)

2.0 A