F-6 System Loading and Heat Dissipation

System Current Loading Example Calculations (40-point
Controller)

Table F.9 Calculating the Current for MicroLogix Accessories

Catalog Number

Device Current Requirements

Calculated Current

at 5V dc (mA)

at 24V dc (mA)

at 5V dc
(mA)

at 24V dc
(mA)

1761-NET-AIC

(1)

when powered by the base unit

communications port, selector switch in the up position

0

120

0

120

Subtotal 1:

0

120

(1) This is an optional accessory. Current is consumed only if the accessory is installed.

Table F.10 Calculating the Current for Expansion I/O

Catalog Number

(1)

n

A

B

n x A

n x B

Number of
Modules

Device Current Requirements (max)

Calculated Current

at 5V dc (mA)

at 24V dc (mA)

at 5V dc (mA)

at 24V dc (mA)

1762-IA8

50

0

1762-IF4

40

50

1762-IF2OF2

1

40

105

40

105

1762-IQ8

50

0

1762-IQ16

2

70

(2)

0

140

(2)

0

1762-IQ32T

170

0

1762-IR4

40

50

1762-IT4

40

50

1762-OA8

1

115

0

115

0

1762-OB8

115

0

1762-OB16

175

0

1762-OB32T

175

0

1762-OF4

40

165

1762-OV32T

175

0

1762-OW8

80

90

1762-OW16

1

140

(2)

180

(2)

140

(2)

180

(2)

1762-OX6I

110

110

1762-IQ8OW6

110

80

Total Modules (6 maximum):

6

Subtotal 2:

435

285

(1) Refer to your expansion I/O Installation Instructions for Current Requirements not listed in this table.

(2) Only applicable to Series B I/O modules.