Rockwell Automation 1762-Lxxxx MicroLogix 1200 Programmable Controllers User Manual

Page 104

Advertising
background image

Publication 1762-UM001G-EN-P - March 2011

A-12 Specifications

Vendor I.D. code

1

Product type code

7

Product code

119

101

103

100

Table A.14 Output Specifications

Specification

1762-OA8

1762-OB8

1762-OB16

1762-OB32T

Table A.15 Output Specifications

Specification

1762-OV32T

1762-OW8

1762-OW16

1762-OX6I

Shipping weight, approx.
(with carton)

200 g (0.44 lbs.)

228 g (0.50 lbs.)

285 g (0.63 lbs.)

220 g (0.485 lbs)

Voltage category

24V dc sink

AC/DC normally open
relay

AC/DC normally open
relay

AC/DC Type C Relay

Operating voltage range

10.2…26.4V dc

5…265V ac
5…125V dc

5…265V ac
5…125V dc

5…265V ac
5…125V dc

Number of outputs

32

8

16

6

Bus current draw, max.

175 mA at 5V dc
0 mA at 24V dc

80 mA at 5V dc (0.40 W)
90 mA at 24V dc (2.16 W)

140 mA at 5V dc (0.70 W)
180 mA at 24V dc
(4.32 W)

(1)

110 mA at 5V dc (0.55 W)
110 mA at 24V dc
(2.64 W)

Heat dissipation, max.

2.7 W at 26.4V dc

2.9 W

6.1 W

(1)

2.8 W

Signal delay, max. –
resistive load

On delay: 0.5 ms
Off delay: 4.0 ms

On delay: 10 ms
Off delay: 10 ms

On delay: 10 ms
Off delay: 10 ms

On delay:
10 ms (max)
6 ms (typical)
Off Delay:
20 ms (max)
12 ms (typical)

Off-state leakage, max.

0.1 mA at 26.4V dc

0 mA

0 mA

0 mA

On-state current, min.

1.0 mA

10 mA

10 mA

100 mA

On-state voltage drop,
max.

0.3V dc at 0.5A

Not applicable

Not applicable

Not applicable

Continuous current per
point, max.

0.5A at 60 °C (140 °F)

2.5 A (Also see “Relay Contact Ratings” on page A-6.) 7A (Also see “Relay

Contact Ratings” on
page A-6.)

Continuous current per
common, max.

2.0 A at 60 °C (140 °F)

8 A

8A

7A (Also see “Relay
Contact Ratings” on
page A-6.)

Continuous current per
module, max.

4.0 A at 60 °C (140 °F)

16 A

16A

30A (Also see Module
Load Ratings 1762-OX6I
on page A-14.

Surge current, max.

2.0 A (Repeatability is
once every 2 s at 60 °C
(140 °F) for 10 ms)

See “Relay Contact Ratings” on page A-6

See “Relay Contact
Ratings” on page A-6.

Power supply distance
rating

6 (The module may not be more than 6 modules away from the power supply.)