Specifications A-15

Analog Modules

Table A.19 Analog Modules Common Specifications

Specification

1762-IF2OF2, 1762-IF4, 1762-IR4, 1762-IT4 and 1762-OF4

Dimensions

90 mm (height) x 87 mm (depth) x 40 mm (width), height including mounting tabs is 110 mm
3.54 in. (height) x 3.43 in. (depth) x 1.58 in. (width), height including mounting tabs is 4.33 in.

Temperature, storage

-40…85 °C (-40…185 °F)

Temperature, operating

-20…65 °C (-4…149 °F)

(1)

Operating humidity

5…95% non-condensing

Operating altitude

2000 m (6561 ft)

Vibration

Operating: 10…500 Hz, 5G, 0.030 in. max. peak-to-peak

Shock

Operating: 30G

Module power LED

On: indicates power is applied.

Recommended cable

Belden 8761 (shielded)
(For 1762-IT4, Shielded thermocouple extension wire for the specific type of thermocouple you are
using. Follow thermocouple manufacturer’s recommendations.)

Agency certification

C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
C-Tick marked for all applicable acts (1762-IR4 and 1762-IT4)

Hazardous environment class

Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 No. 213)

Noise immunity

NEMA standard ICS 2-230

Radiated and conducted emissions

EN50081-2 Class A

Electrical/EMC:

The module has passed testing at the following levels:

ESD immunity
(IEC1000-4-2)

4 kV contact, 8 kV air, 4 kV indirect

Radiated RF immunity
(IEC1000-4-3)

10 V/m, 80…1000 MHz, 80% amplitude modulation, +900 MHz keyed carrier

EFT/B immunity
(IEC1000-4-4)

2 kV, 5 kHz

Surge transient immunity
(IEC1000-4-5)

1 kV galvanic gun

Conducted RF immunity
(IEC1000-4-6)

10 V, 0.15…80 MHz

(2)

(3)

(1) Refer to the module’s Installation Instruction for exact operating temperature range.

(2) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to 1000 MHz.

(3) For grounded thermocouples, the 10 V level is reduced to 3V.