Communication Connections 4-5

Make a DF1 Point-to-Point Connection

You can connect the MicroLogix 1200 programmable controller to your
personal computer using a serial cable (1761-CBL-PM02) from your personal
computer’s serial port to the controller via Channel 0 and/or the
Programmer/HMI Port (for 1762-LxxxxxR only). The recommended
protocol for this configuration is DF1 Full-duplex.

We recommend using an Advanced Interface Converter (AIC+), catalog
number 1761-NET-AIC, as your optical isolator, as shown on the following
page. See page 4-13 for specific AIC+ cabling information.

(1) Series C or higher cables are required.

Use a Modem

You can use modems to connect a personal computer to one MicroLogix 1200
controller (using DF1 Full-duplex protocol), to multiple controllers (using
DF1 Half-duplex protocol), or Modbus RTU Slave protocol via Channel 0, as
shown in the following illustration. (See Appendix E for information on types
of modems you can use with the micro controllers.

TERM

A

B

COM

SHLD

CHS GND

TX

TX

PWR

TX

DC SOURCE
CABLE

EXTERNAL

1761-CBL-AM00 or 1761-CBL-HM02

(1)

1747-CP3 or 1761-CBL-AC00

MicroLogix 1200
Channel 0 or Programmer/HMI Port

24V dc
MicroLogix 1200 provides power to the AIC+ or an
external power supply may be used.

Personal Computer

IMPORTANT

Do not attempt to use DH-485 protocol through
modems under any circumstance.