Shock

Operating: 30G; 3 pulses each direction, each axis
Relay Operation: 7G
Non-Operating: 50G panel mounted (40G DIN Rail mounted); 3 pulses each direction, each axis

Agency certification

UL 508

C-UL under CSA C22.2 no. 142

Class I, Div. 2, Groups A, B, C, D
(UL 1604, C-UL under CSA C22.2 no. 213)

CE/C-Tick compliant for all applicable directives/acts

Electrical/EMC

The controller has passed testing at the following levels:

EN 61000-4-2: 4 kV contact, 8 kV air, 4 kV indirect

EN 61000-4-3: 10V/m, 80 to 1000 MHz, 80% amplitude modulation, +900 MHz keyed carrier

EN 61000-4-4: 2 kV, 5 kHz; communications cable: 1 kV, 5 kHz

EN 61000-4-5: communications cable 1 kV galvanic gun
I/O: 2 kV CM (common mode), 1 kV DM (differential mode)
AC Power Supply: 4 kV CM (common mode), 2 kV DM (differential mode)
DC Power Supply: 500V CM (common mode), 500V DM (differential mode)

EN 61000-4-6: 10V, communications cable 3V

Terminal screw torque

0.791 Nm (7 in-lb) rated

(1) Do not allow the total load power consumed by the 5V dc, 24V dc, and sensor power outputs to exceed 12W.

(2) Do not allow the total load power consumed by the 5V dc, 24V dc, and sensor power outputs to exceed 16W.

See Appendix F for system validation worksheets.

Table A.1 General

Attribute

1762-

L24AWA
L24AWAR

L24BWA
L24BWAR

L24BXB
L24BXBR

L40AWA
L40AWAR

L40BWA
L40BWAR

L40BXB
L40BXBR

Table A.2 Input Specifications

Attribute

1762-L24AWA
1762-L40AWA
1762-L24AWAR
1762-L40AWAR

1762-L24BWA, -L24BXB, -L40BWA, -L40BXB
1762-L24BWAR, -L24BXBR, -L40BWAR, -L40BXBR

Inputs 0 through 3

Inputs 4 and higher

On-state voltage range

79…132V ac

14…24V dc
(+10% at 55 °C/131 °F)
(+25% at 30 °C/86 °F)

10…24V dc
(+10% at 55 °C/131 °F)
(+25% at 30 °C/86 °F)

Off-state voltage range

0…20V ac

0…5V dc

Operating frequency

47…63 Hz

0 Hz…20 kHz

0 Hz…1 kHz
(scan time dependent)

On-state current:

minimum

nominal

maximum

5.0 mA at 79V ac

12 mA at 120V ac

16.0 mA at 132V ac

2.5 mA at 14V dc

7.3 mA at 24V dc

12.0 mA at 30V dc

2.0 mA at 10V dc

8.9 mA at 24V dc

12.0 mA at 30V dc