Diagnostics Methods

Chapter 7

7-10

Also, the scanner configured as the master on a peer-to-peer
communication channel declares a peer-to-peer communication minor fault
when it cannot successfully communicate with a slave after two
consecutive retries.

Important: Once set, the peer-to-peer and backup communication minor
status bit remain set until you reset it.

Table 7.B

I/O Channel Indicators for All Scanner Modules

Indicator

Status

Description

CHx

ON

Communication between scanner module and the I/O chassis

on the corresponding I/O channel is properly established.

Configured for

I/O Scanning

FLASHING There is a fault on one or more of the I/O chassis on the

corresponding I/O channel.

OFF

No I/O chassis are configured on the corresponding I/O

channel or the channel is inactive.

CHx

ON

The channel is functioning properly.

Configured for

peerĆtoĆpeer

communication

FLASHING The input file is too small at the processor receiving data. The

slave or master does not exist. Communication retry.

OFF

The channel is inactive.

CHx

ON

The channel is functioning properly.

Configured for

backup

communication

FLASHING The input file is too small at the processor receiving data. The

partner is not responding.

OFF

The channel is inactive.

Table 7.C shows the DH/DH+ status indicators for 1775-S5, -SR5
scanner modules.

Table 7.C

DH/DH+ Status Indicators for 1775ĆS5, ĆSR5 Scanner Modules

Indicator

Status

Description

XMTG

ON

transmitting a message

RCVG

ON

receiving a message

RDY

ON

ready to transmit a message

ERR

ON

programming or communication error detected

DIS

ON

DH/DH+ channel is disabled

DH/DH+ Indicators