Binary Command Language

Appendix A

A-20

The following example command block uses the read I/O word command
to request the data and force information for the output word representing
rack 6, module group 4:

STX

02

ISC

01

SIZ

03

CMD

23

34

DAT

00

ETX

03

CHK

60

The data bytes store:

lower byte of the I/O address (34 hex)
upper byte of the I/O address (00 hex)

The processor responds to a read I/O word command with one of the
following response codes:

Response Codes

Hex

Description

00

Success

03

Forces unavailable

04

Address unknown

06

Access not allowed

08

Address not complete

When the processor returns a success response, the data buffer also
contains the data stored at the requested address, and force-on and
force-off masks associated with that data. The following example shows a
response block for a read I/O word command when forces exist:

STX

02

OSC

01

SIZ

07

RSP

00

61

1C

02

CHK

92

DAT

86

80

00

ETX

03

The data bytes store:

lower byte of the data word (61 hex)
upper byte of the data word (1C hex)
lower byte of the force-on mask (02 hex)
upper byte of the force-on mask (86 hex)
lower byte of the force-off mask (80 hex)
upper byte of the force-off mask (00 hex)