Binary Command Language

Appendix A

A-9

Table A.C

Response Code

HEX code

Response

Description

00

Success

Operation was completed as requested.

01

Size Too Big

Operation stopped because the response was too big to fit in the

response block. Success or failure depends on the operation.

02

Available

Interpretation of this response depends on the operation. See the

appropriate command descriptions for details.

03

Unavailable

Interpretation of this response depends on the operation. See the

appropriate command descriptions for details.

04

Address Does Not Exist

The specified address has not been allocated.

05

Address Invalid

This response is returned when the specified start address is valid, but

another address used in the operation has not been allocated.

06

Access Not Allowed

The channel does not have access to the area specified for the

purpose requested.

07

Allocated

The function or resource requested is allocated and therefore

unavailable (unless it is already allocated to your channel).

08

Address Not Complete

The address given is not specified to a low enough level to perform

the requested function.

09

Unknown Command

The scanner does not recognize the command code.

0A

Invalid Parameter

A parameter in the command block is invalid.

0D

Processor Error

0E

Processor Error

0F

No Privilege

One or more privileges required for the attempted operation are not

assigned to the channel.

FF

Unknown Failure

The function failed for a reason which cannot be described by any

other response code.

Initializing Communications

To initiate communications with the scanner the master sends a break
character followed by a CCR. The CCR should have the reset
communications bit (bit 0) of the control code set. This instructs the
scanner to return to its initial communications state, including resetting the
command block sequence and the response block sequence count.

The master must see break go away before sending the CCR. The scanner
sends break for a character timeout period. The scanner identifies a break
character as any high state (voltage) which remains on the line longer than
the time required to transmit one character (byte). The approximate
character times are listed in Table A.D.