Diagnostics Methods
Chapter 7
7-16
Table 7.H
Data Sent in Response to a Diagnostic Status Command
Byte:
Bit:
Description:
1
Operating status of PLC-3 processor
0-1
00 = Program mode
01 = Test mode
10 = Run mode
2
Not used
3
0 = Normal
1 = Major processor fault
4
0 = Normal
1 = Shutdown request
5
0 = Normal
1 = Shutdown in effect
6Ć7
Not used
2
Type of station interface and processor
0Ć3
6 = scanner
4Ć7
4 = PLC-3 processor
3
all
Current context stored in bits 4 thru 7
4
all
Thumbwheel
5Ć6
all
Mode control word
The extended address of the mode control word is E0.0.0.8
7Ć8
all
Starting byte address of the diagnostic counters.
9
Series and revision number of the module.
Even though the scanners are series A, they appear as series E modules
0Ć3
0 = Revision A scanner
1 = Revision B scanner
etc.
4Ć7
0 = Series A 1 = Series B
etc.
10
Type of channel communications
0Ć1
0 = Inactive
1 = DH
2 = DH+
3 = other
2Ć3
0 = A/G or earlier S5 or SR5
1 = A/H or later S5
2 = A/H or later SR5
3 = unused
4Ć7
unused
11Ć14
all
The physical address of the unused word of PLC-3 system memory.
This is the physical address corresponding to the extended address
E60.0.0.0
15Ć18
all
The total number of words in the PLC-3 system memory
(both used and unused)