Scanner Hardware and Installation

Chapter 1

1-4

Pass and Fail Indicators

The indicators labeled PASS and FAIL (Figure 1.2) keep you informed
about the general condition of the scanner:

PASS (green)

FAIL (red)

Meaning

on

off

normal operation

off

on

module fault

on

on

powerĆup or system reset

off

off

system is not on or module has lost power

Forces Enabled Indicator

The yellow indicator labeled FORCE (Figure 1.2) illuminates when I/O
forcing is enabled in the system.

I/O Channel Status Indicators

The four green indicators labeled CH1, CH2, CH3, and CH4 (Figure 1.2)
correspond to one of the four I/O channels.

Indicator

Status

Description

CHx

ON

Communication between scanner module and the I/O chassis

on the corresponding I/O channel is properly established.

Configured for

I/O scanning

FLASHING There is a fault on one or more of the I/O chassis on the

corresponding I/O channel.

OFF

No I/O chassis are configured on the corresponding I/O

channel or the channel is inactive.

CHx

ON

The channel is functioning properly.

Configured for

peerĆtoĆpeer

communication

FLASHING The input file is too small at the processor receiving data. The

slave or master does not exist. Communication retry.

OFF

The channel is inactive.

CHx

ON

The channel is functioning properly.

Configured for

backup

communication

FLASHING The input file is too small at the processor receiving data. The

partner is not responding.

OFF

The channel is inactive.