Rockwell Automation 1775-S5_SR5,D17756.5.5 User Manual PLC-3 FAMILY I/0 User Manual

Page 150

Advertising
background image

Binary Command Language

Appendix A

A-22

The processor responds to a write word command with one of the
following response codes:

Response Codes

Hex

Description

00

Success

04

Address unknown

06

Access not allowed

08

Address not complete

0F

No privilege

If any code other than success is returned, no data is written into memory.
The following response block shows a successful write word command:

STX

02

OSC

01

SIZ

01

RSP

00

ETX

03

CHK

07

Write Block Command

Hex: 20

Parameters: Starting address, number of words, and the new data

Description: The following example command block writes new data into
the first 3 words of integer file 0:

STX

02

ISC

01

SIZ

0E

CMD

20

3C

05

00

ETX

03

CHK

9D

00

00

03

DAT

00

10

02

08

00

7D

8E

The data bytes store:

address mask (3C hex)
first to fourth address bytes (05, 00, 00, 00 hex)
lower and upper bytes of:

- size word (03, 00 hex)
- first data word (10, 02 hex)
- second data word (08, 00 hex)
- third data word (7D, 8E hex)