Addressing DH and DH+ Data Transfers

Chapter 5

5-3

The S5 and SR5 scanners offer four different addressing methods for use in
DH and DH+ assignment commands:

PLC-2 Logical Data Addressing
PLC-3 Logical Binary Addressing
Logical ASCII Data Type Addressing
Logical ASCII Word Range Addressing

Although the scanner can transmit and receive any of these addressing
methods, not all remote stations are able to interpret these methods.
Table 5.A indicates which addressing methods are accepted by
other controllers.

Table 5.A

Acceptable Addressing Methods

Accepted by Receiving Station

PLCĆ3

Addressing

PLCĆ2

KA

S5

PLCĆ4

PLCĆ5

PLCĆ5/250

PLCĆ2 Logical Data

X

X

X

X

X

X

PLCĆ3 Logical Binary

--

X

X

--

--

--

Logical ASCII Data Type

--

--

X

--

X

X

Logical ASCII Word Range

--

--

X

--

X

X

A PLC-2 logical data address references a dedicated file in the remote
station. This addressing method simply provides an offset into this PLC-2
data table or PLC-2 compatibility file. The offset is interpreted as octal if a
leading zero is included, otherwise the scanner interprets the number as
decimal.

The receiving station must be able to interpret this form of addressing (see
Table 5.A).

Addressing Words

To address a group of consecutive words in the remote stations memory,
use the following format:

Format:

Example:

offset, size

$047,20

Using PLCĆ2 Logical Data

Addressing