I/O Communication

Chapter 3

3-2

Table 3.A

I/O Scan per I/O Chassis in Milliseconds

Number of Active I/O Channels

bps Chan 4 Config

1

2

3

4

57.6k

Not DH/DH+

DH/DH+

7

8

7

8

7.5

9

8

N/A

115.2k

Not DH/DH+

DH/DH+

4.5

5

5

6

5

7

6.5

N/A

230.4k

Not DH/DH+

DH/DH+

3

N/A

3.5

N/A

5

N/A

6

N/A

Each I/O chassis that you add to the scanning sequence list (including
repeated I/O chassis in the list) increases the I/O scan time.

When you add block-transfer modules to the channel, the I/O scan time
increases by approximately 1ms per adapter on all channels while the
scanner executes the block-transfer instruction.

Calculating BlockĆTransfer Times

The time required to complete a block transfer depends on the number of:

I/O channels on the scanner that contain block-transfer I/O modules
active I/O channels on the scanner
entries in the I/O chassis scanning sequence list for the channel
block-transfer I/O modules on the channel

To calculate the time required for the scanner to execute all block transfers
on the channel and be ready to execute the block-transfer again:

1. Determine the number of active I/O channels on the scanner.

2. Determine the number of I/O channels with block-transfer

I/O modules.

3. Determine the nominal block-transfer time (see Table 3.B).