Binary Command Language

Appendix A

A-31

Read Section Size Command

Hex: 19

Parameters: Address of section to read

Description: The following example command block requests the size of
the data table in context 1:

STX

02

ISC

08

SIZ

04

CMD

19

03

DAT

03

01

ETX

03

CHK

31

The data bytes store:

address mask (03 hex)
first and second address bytes 903, 01 hex)

The processor responds to a read section size command with one of the
following response codes:

Response Codes

Hex

Description

00

Success

04

Address unknown

06

Access not allowed

If the processor returns a success response code, the next four bytes
contain the section size, with the least significant byte transmitted first.
The two bytes following the section size contain the number of next levels
of addressing.

For example, in context 1 of the data table, the number of next levels
corresponds to the number of data table sections such as output, input, or
integer. And in the integer section, the number of next levels corresponds
to the number of integer files.

The following example response block shows successful read section
size command:

STX

02

OSC

14

SIZ

07

RSP

00

08

28

00

CHK

69

DAT

00

19

00

ETX

03