Peerćtoćpeer and backup communication – Rockwell Automation 1775-S5_SR5,D17756.5.5 User Manual PLC-3 FAMILY I/0 User Manual

Page 51

Advertising
background image

I/O Communication

Chapter 3

3-3

Table 3.B

NominalĆBlockĆTransfer Times in Milliseconds for a BlockĆtransfer

Instruction

Channels with blockĆ

transfer I/O modules

Number of active channels

transfer I/O modules

1

2

3

4

1

27

27

28

35

2

x

29

30

36

3

x

x

31

38

4

x

x

x

40

4. Count the number of block-transfer I/O modules on the channel. If

the chassis containing a block-transfer I/O module appears more than
once in the I/O chassis scanning list, count the module once each time
the chassis appears in the list.

5. Count the number of entries in the I/O chassis scanning sequence list

for the channel.

6. Calculate the time between block transfers as follows:

T = (NBT x NM)ms + (NE – 1) x 7ms

Where:

Is the:

T

time between block transfers

NBT

nominal blockĆtransfer time (Table 3.B)

NM

number of blockĆtransfer modules (step 4)

NE

number of entries in the I/O scan list

PLC-3 family controllers can communicate with other PLC-3 family
controllers using peer-to-peer or backup communication channels.

PeerĆtoĆPeer Communication

A peer-to-peer communication channel includes one PLC-3 or PLC-3/10
controller configured as the master and up to six PLC-3 or PLC-3/10
controllers configured as slaves. The master communicates with all slaves
on the channel, while each slave communicates only with the master
(Figure 3.1).

Also, when configured in a backup system, the backup slave receives all
input data that are sent to the primary slave if the slave numbers are
the same.

PeerĆtoĆPeer and Backup

Communication

Advertising