Rockwell Automation 1775-S5_SR5,D17756.5.5 User Manual PLC-3 FAMILY I/0 User Manual

Page 79

Advertising
background image

Addressing DH and DH+ Data Transfers

Chapter 5

5-5

When you use a PLC-3 logical binary address, the scanner transmits the
address to the remote station as a six level extended address. This
addressing method is normally reserved for communication between
PLC-3 scanners since the receiving station must be able to interpret this
form of addressing (see Table 5.A). The following rules apply when
specifying a PLC-3 logical binary address:

1. You must define symbolic addresses to either the word level or the

file level of specification.

2. A word address can be either a:

logical word address
symbolic address of a word
symbolic file address followed by a colon (:) and an offset
extended address specified to the word level

3. You must precede a size specification with a word address and a

comma (,).

4. You must precede an offset specification with a file address and a

colon (:).

5. You must precede a bit number with a word address and a slash (/).

6. You can use extended addressing to access the pointer section

of memory.

Addressing a File

To address a file, use either a file address or a file symbol:

Format:

Example:

fileaddr

$N0

filesym

@FILE_A

For assignment commands that copy data from one file to another, both the
source and the destination file must be exactly the same size.

Using PLCĆ3 Logical Binary