Rockwell Automation 1775-S5_SR5,D17756.5.5 User Manual PLC-3 FAMILY I/0 User Manual

Page 39

Advertising
background image

Configuring the Scanner through LIST

Chapter 2

2-13

4 - Backup Operation

Select the

Backup Operation

option from the configuration screen to

configure the DH and DH+ station numbers when backed up. See
Table 2.A.

Table 2.A

Backup Operation Options

If backup is:

The DH and DH+ station number of the backup scanner module:

Selected

is automatically modified before and after switchover. This allows you to

have identical configurations in both the primary and the backup

processor.

Not selected

remains the same both before and after switchover. The primary and

backup processors must have unique station numbers.

Regardless of which mode you select, both the primary and the backup DH
and DH+ channels are active. There is no selection for the backup DH or
DH+ channel to remain silent on the link until switchover.

When you select backup operation, you assign the same DH or DH+
station number to both the scanner module in the primary processor and
the one in the backup processor.

As long as the primary processor is controlling the outputs, the station
address of the DH or DH+ channel in the backup processor is modified.
Table 2.B and Table 2.C show the station number modifications for DH
and DH+, respectively. At switchover, the DH or DH+ station number in
the backup processor assumes the station address assigned to it with the
LIST function.

Table 2.B

DH Station Numbers for 1775ĆS5, ĆSR5 Modules

If the station address between:

The backup scanner module assumes a station

address that is:

000 and 276

8

100

8

higher than the assigned station number

300

8

and 376

8

100

8

lower than the assigned station number

Important: Do not give the 1775-S5, -SR5 module the reserved station
address of 377

8

; and, when you select the backup operation, you cannot

give the module a station address of 277

8

.