DH and DH+ Communication

Chapter 4

4-6

Ladder Program

The first link in the communication process is your ladder program. You
send a DH/DH+ command message by means of the message (MSG)
instruction (Figure 4.2).

When the rung becomes true, the processor informs the scanner to begin
sending command(s) across the link. At the same time, bits in a control
file word change their state (Table 4.B) to reflect the status of the
message instruction.

Important: Once enabled, even if the rung becomes false, the scanner
continues to send commands across the DH/DH+ network until the
message is done or errors.

Table 4.B

The Status of Bits in a Control File Word

When the:

The processor:

message instruction is true

sets the enable bit (16) and the latchĆenable

bit (12)

scanner receives the message instruction

sets the request bit (17)

scanner begins operation

sets the busy bit (14)

scanner completes operation

resets the busy bit (14) and sets either the

done bit (15) or the error bit (13)

rung becomes false

resets the request bit (17), busy bit (140),

enable bit (16), and the latchĆenable bit (12)

rung becomes true a second time

resets the done bit (15) or the error bit (13)

message errors appear

sets the error bit (13) and records the error

code in bits 00 thru 07

You can program the message instruction with either:

a single message command (see chapter 6) that can be up to 76

characters long.

the name of a DH/DH+ message procedure that contains a group of

commands and is stored in the message area of PLC-3 or
PLC-3/10 memory.