Setting Backup System Functions
On the bottom edge (Figure 1.7) near the rear of the scanner is a set of 4
switches. If you are using a backup configuration, then you can set
switches 2 and 3 to define the switchover type. For detailed information
on backup, refer to the PLC-3 Backup Concepts Manual (publication
1775-6.3.1).

Figure 1.7

Setting Backup System Functions

switchback

If you are operating a backup system,

then set these switches to set up the

type of switchover.

Switchover Type

Switch

2

3

Auto with controllable

Auto with no switchback

down

up

Manual

down

up
up

up

up
down

both

primary

backup
both

System

(primary

or backup)

1

If you are not operating a backup system, then set switches 2 and 3 to the UP position.

1

2

3

4

Always Up

Up (away from board)

Down (toward board)

The backup switches for scanners other than thumbwheel number 1 should
be set away from the board.

Installing the Scanner

After you configure the scanner, insert the scanner into any slot of a:

PLC-3 processor chassis (cat. no. 1775-A1, -A2)
PLC-3/10 processor chassis (cat. no. 1775-A3)

PLC-3 and PLC-3/10 CPUs, scanners, and memories are not
interchangeable.