Rockwell Automation 1775-S5_SR5,D17756.5.5 User Manual PLC-3 FAMILY I/0 User Manual

Page 34

Advertising
background image

Configuring the Scanner through LIST

Chapter 2

2-8

PeerĆtoĆPeer Master Configuration

When you configure a channel as a master on a peer-to-peer
communication channel, you must enter the following parameters:

Parameter

Description

Master number

identifies the master for communication with the slaves. Each peerĆtoĆpeer

communication channel can have one master only. The master number and all

slave numbers must be unique and selected from numbers 81 through 89.

Slave numbers

identify the slaves that communicate with the master. Each master can

communicate with up to 6 slaves. The slave number must be unique and

selected from numbers 81 through 89.

Input files

identify the files that receive data from each slave. You must specify an input

file for each slave in the input image section of the data table. If you do not

make a selection, the file defaults to input file 1. The files also must be large

enough to store the data from each slave's output file. If the file is not large

enough, the processor declares a minor fault.

Output files

identify the files that send data to each slave. You must specify an output file

for each slave in the output image section of the data table. If you do not make

a selection, the file defaults to output file 1.

LIST displays the size of the input and output files. For example,
I1:0

19 shows that input file 1 contains 20 octal words. You can create

a larger file by entering the last word desired in the file when prompted for
the file number in LIST. By entering I1:50 for the input file, the system
will automatically increase input file 1 to 50 octal words.

To delete slave entries from the list, press:

slave entry /d [Return]

PeerĆtoĆPeer Slave Configuration

When you configure a channel as a slave on a peer-to-peer communication
channel, you must enter the following parameters:

Parameter

Description

Slave number

identifies the slave that communicates with the master. The slave number must

be unique and selected from numbers 81 through 89.

Master number

identifies the master on the channel. The master number and all slave

numbers must be unique and selected from numbers 81 through 89.

Input file

identifies the file that receives data from the master. This file must be in the

input image section of the data table. If you do not make a selection, the file

defaults to input file 1. This file must be large enough to store the data from the

master's output file. Otherwise the processor sets the peerĆtoĆpeer minor fault

bit.

Output file

identifies the file that sends data to the master. This file must be in the output

image section of the data table. If you do not make a selection, the file defaults

to output file 1.