Addressing dh and dh+ data transfers chapter 5 – Rockwell Automation 1775-S5_SR5,D17756.5.5 User Manual PLC-3 FAMILY I/0 User Manual
Page 91

Addressing DH and DH+ Data Transfers
Chapter 5
5-17
Table 5.E
Logical ASCII Word Range Addressing
Word Range Addressing
Description
#H024$’D1:0’ = $D1:0,2
write two words beginning with decimal file 1, word
0 into remote station 24's decimal file 1, word 0.
#H040$’@PUNCH’ = $A1:0
write the data stored at ascii file 1, word 0 into
remote station 40 which will store the data at the
address defined by symbolic address @PUNCH.
This symbol must be created and defined in the
remote station.
#H014$’T0:5’ = $T4,6
write 6 contiguous words beginning with $TCTL:4,
into remote station 14 beginning with timer five. In
this example, timers 4 and 5 (3 words each) would
be transferred complete.
#H014$’C5’ = $C4,5
write 5 contiguous words beginning with $CCTL:4
into remote station 14 beginning with counter 5. In
this example, $CCTL:4, $CPRE:4, $CACC:4,
$CCTL:5, and $CPRE:5 would be transferred into
$CCTL:5, $CPRE:5, $CACC:5, $CCTL:6, and
$CPRE:6 respectively.