background image

Binary Command Language

Appendix A

A-24

When the processor receives a read-modify-write command,
it (Figure A.3):

1.

Reads the data at the specified address.

2.

Performs a logical AND operation between the data read in step 1 and
the AND mask.

3.

Performs a logical OR operation between the result of step 2 and the
OR mask.

4.

Writes the result of step 3 into the word at the specified address.

Figure A.3

ReadĆModifyĆWrite Operation

Bit Pattern

Description

1111000011110000

Initial state of specified word

0101010101010101

AND mask

0101000001010000

Result of logicalĆAND operation

1010000001011111

Final result

The processor responds to a read-modify-write command with one of the
following response codes:

Response Codes

Hex

Description

00

Success

04

Address unknown

06

Access not allowed

08

Address not complete

0F

No privilege

The following response block shows a successful read-modify-write
command:

STX

02

OSC

01

SIZ

01

RSP

00

ETX

03

CHK

07