DH/DH+ Error Codes

Apendix B

B-7

Error Code

Meaning

Associated

Commands

Error Type

209

local

all

Not of DH message type.

210

local

all

Use of a nonĆPLCĆ3 type address in a local address operand.

211

local

all

In an assignment command, one of the local files does not exist, or the word

specified is beyond the end of the file.

212

local

create

During CREATE command execution, the scanner was not able to create any

symbols.

213

local

all

A local file exists, but the action specified refers to addresses beyond the end of

the file. Possible causes include:

In a word assignment statement, the offset is greater than the file size.

In a word range assignment statement, the sum of the base address and the

offset is greater than the total file size.

In a file assignment statement, the destination file is smaller than the source

file. If the source file is remote, a single packet is fetched from the remote

station's file.

214

local

all

Local source and destination files differ in size.

215

local

all

The value resulting from operations specified on the left side of an assignment

statement does not fit into the destination specified on the right side:

The source is in the H section and the destination is in the N section, but the

number is too large (i.e., outside the range -32768 to +32767).

A word is transferred from a binary section (I, O, or B section) to the N or C

section and the highĆorder bit is a 1.

The destination is in the decimal section, but the number is not a valid BCD bit

pattern.

217

local

all

More than eight levels specified in file address.

218

local

all

File size changed between packets of a multiĆpacket transaction.

Destination not created.

230

local

all

Reply packet too small.

231

reply

PLCĆ3 read and

write

Error in converting the block address (major section 63, context 15, or section

15).

232

reply

PLCĆ3 read and

write

Three or fewer addressing levels specified for a PLCĆ3 word address.

233

reply

PLCĆ3 read and

write

Conversion of a file address to a block address resulted in more than nine

addressing levels.

234

reply

PLCĆ3 read and

write

Symbolic address not found.

235

reply

PLCĆ3 read and

write

Symbolic address is of length zero or is longer than eight bytes.