Configuring the Scanner through LIST

Chapter 2

2-7

To delete entries from the list, press:

entry

/

d

[Return]

When forming this list, remember:

Selection of I/O rack numbers greater than 37

8

increases the program

scan time.

I/O rack numbers that are not assigned consecutively cause greater

memory requirements because memory has to be allocated for the
unused racks.

You can connect up to 32 I/O adapters to one I/O communication

channel on a scanner.

You can assign up to 16 different I/O rack numbers to one scanner.

For duplicate I/O addressing (complementary I/O or parallel output

configurations), you must have two chassis with the same assigned I/O
rack number and I/O group number on different I/O communication
channels of the same scanner.

Refer to the PLC-3 Family Controller Installation and Operation Manual
(publication 1775-6.7.1) for detailed information on complementary and
duplicate I/O configurations.

ATTENTION: Do not assign the same I/O rack number and
I/O group number to two chassis on the same I/O
communication channel. Failure to observe this warning could
result in equipment damage and/or unpredictable machine
operation with injury to personnel.

The controller uses assigned I/O rack numbers 77

8

, 177

8

, 277

8

, 377

8

for

internal communication. Do not assign these numbers to an I/O rack
(although you can use the associated addresses for internal storage).

For detailed information on 1/2-slot, 1-slot, and 2-slot I/O addressing
considerations, refer to the Remote I/O Adapter (Cat. No. 1771-ASB)
User’s Manual (publication 1771-6.5.83).