DH and DH+ Communication

Chapter 4

4-11

Accessing a PLC-3 Processor from a PLC-2 Processor
While a PLC-3 controller can address any area of a PLC-2 data table, a
PLC-2 reads an input file that is a part of the PLC-3 data table. That file is
the PLC-3 input file with a number that corresponds to the station number
of the PLC-2 station. For example, the read/write files assigned to PLC-2
stations 1 to 100 (octal) is:

PLCĆ2 compatible station number in octal

Assigned input file for read/write access

000

I008

001

I001

002

I002

003

I003

004

I004

005

I005

006

I006

007

I007

010

I010

011

I011

012

I012

.

.

.

.

.

.

077

I077

100

I100

Station address 000 is assigned to input file I008. Otherwise PLC-3 input
files with an 8 or 9 in their addresses are not used for read/write access by
a PLC-2 station.

The PLC-2 station can use either protected or unprotected commands to
access its assigned PLC-3 file. However, the PLC-2 station cannot access
its assigned file until that file is created and allocated at the PLC-3 station.
To create a file, refer to the user’s manual for your programming terminal.

You can have two PLC-3 stations communicate with each other as if they
were PLC-2 stations. To do this, allocate the appropriate PLC-2
addressing format (see chapter 5) in the assignment commands. Similarly,
a computer can send PLC-2 commands to a PLC-3 station by using the
appropriate message packet formats.