Diagnostics methods chapter 7 – Rockwell Automation 1775-S5_SR5,D17756.5.5 User Manual PLC-3 FAMILY I/0 User Manual
Page 127

Diagnostics Methods
Chapter 7
7-15
Table 7.G
DH+ Diagnostic Counters
Byte:
This counter increments when the scanner:
1 & 2
successfully sent a message
3 & 4
successfully received a message
5
can not deliver a message due to a NAK or after using up maximum
retries
6
did not receive a response before the response timeout value was
reached
7
received a NAK
8
must send a message retry as a result of CRC error, illegal length, not
its destination, the source was not the expected station, or a timeout
9
sent a NAK because there was no memory available
10
sent a NAK because of the received message contained an undefined
LSAP
11
receives a message which was received previously
12
has to send a token pass retry
13
receives an aborted packet
14
receives a packet that had a CRC error
15
receives an illegal size packet which was either less than 3 bytes or
larger than 271 bytes
16
detects a duplicate token on the link
17
recovers from a duplicate node condition
18
detects a link dead timeout