Ladder logic program – Rockwell Automation 2707-NP DTAM PLUS GETTING STARTED USER MANUAL User Manual
Page 68
Advertising
![background image](/manuals/580272/68/background.png)
Chapter 7
SLC Application File
7–2
MOV
MOVE
Source
0
Dest
N7:0
0
MOV
MOVE
Source
0
Dest
N7:1
3
S:1
15
Rung 2:0
Reset the DTAM Plus Advisor registers during the first scan of the SLC 500.
Rung 2:1
This timer drives the SQO instructions once per second.
TON
TIMER ON DELAY
Timer
T4:0
Time Base
0.01
Preset
100
Accum
9
T4:0
DN
( EN )
( DN )
SQO
SEQUENCER OUTPUT
File
#N10:0
Mask
FFFF
Dest
N7:22
Control
R6:0
Length
40
Position
2
T4:0
DN
( EN )
( DN )
Rung 2:2
This sequencer simulates the gallons value for screen #22 (TANK LEVEL) in the DTAM Plus.
There are 40 decimal values pre-loaded into #N10:0
Ladder Logic Program