Publication 2711P-UM004B-EN-P - March 2007

DeviceNet Overview 13

DeviceNet Network (NET) Status Indicator

This bi-color (green/red) LED indicates the status of the
communication link.

Condition

Status

Indication

Off

Not powered

Device is not online.

Not online

The device has not completed the
Dup_MAC_ID test yet.

The device may not be powered; look
at the Module Status LED.

Flashing green

(1)

(1)

The flash rate of the LED is approximately 1 flash per second. The LED should be on for approximately 0.5
seconds and off for approximately 0.5 seconds.

Online

Device is online, but has no
connections in the established state.

Not connected

The device has passed the
Dup_MAC_ID test, is online, but has
no established connections to other
nodes.

Green

Link okay, online, connected

The device is online and has
connections in the established state.

Flashing red

(1)

Connection timeout

One or more I/O connections are in
the timed-out state.

Red

Critical link failure

Failed communication device. The
device has detected an error that has
rendered it incapable of
communicating on the network
(Duplicate MAC ID or Bus-off).

Check network integrity and
communication rate of all devices.
Then cycle power to the card by
shutting down and cycling power to
your computer.

ATTENTION

Extensive use of change-of-state connections, particularly with
rapidly changing data, can adversely impact the available
DeviceNet network bandwidth. If the network bandwith
becomes consumed, some devices may only be able to
communicate intermittently. This can result in timeout errors
and possible loss of data. If timeouts occur, consider changing
the connection type for some of the change-of-state
connections to cyclic or polled.