Configure rsnetworx for devicenet, Configure slave i/o for the 1756-dnb module – Rockwell Automation DeviceNet Communications for PanelView Plus and PanelView Plus CE User Manual
Page 60

Publication 2711P-UM004B-EN-P - March 2007
60 Configure the Terminal as a Scanner
Configure RSNetWorx for
DeviceNet
In this section, you will use RSNetWorx for DeviceNet to configure
slave I/O for the 1756-DNB DeviceNet module and map the I/O to the
PanelView Plus terminal.
Before downloading the scanlists to the PanelView Plus and
1756-DNB module, the devices must be in Idle mode.
• For the PanelView Plus, load the application but do not run it.
• For the 1756-DNB module, put the ControlLogix 1756-L63
processor in Program mode. This action will clear the run bit
Local:2:O.CommandRegister.Run.
Configure Slave I/O for the 1756-DNB Module
To configure the slave inputs and outputs in the 1756-DNB module
you must be online.
1. In the RSNetWorx for DeviceNet dialog, double-click the
1756-DNB icon to open the 1756-DNB properties dialog.