Rockwell Automation DeviceNet Communications for PanelView Plus and PanelView Plus CE User Manual

Page 42

Advertising
background image

Publication 2711P-UM004B-EN-P - March 2007

42 Configure the Terminal as a Slave Device

6. Select the PanelView Plus device and click > to add the device

to the scanlist.

The Automap on Add checkbox is selected. When you add the
device to the scanlist, the slave inputs and outputs are
automatically added to the input and output tables.

7. Select the Input tab to verify that the PanelView Plus I/O is

mapped to the Input Assembly Data file.

The DINT slave output (Slave_Output) created for the
PanelView Plus terminal in RSLinx Enterprise software resides in
the first 4 bytes of the 1756-DNB input table.

TIP

If the Automap on Add checkbox was not checked, you
would need to manually map the data on the Input tab.

Advertising