36 Configure the Terminal as a Slave Device

6. Under Change of State / Cyclic, set these parameters to use

Cyclic I/O messaging:

• Select Cyclic
• Input Size = 4
• Output Size = 4

The configuration will transfer 4 bytes of input data and 4 bytes
of output data using cyclic I/O messaging.

7. Click OK to save the data.

Map the I/O to the PanelView Plus Image Table

You must map the I/O data to the PanelView Plus image table so that
it can be scanned by the 1756-DNB DeviceNet module.

1. Select the Input tab to map the input data to the image table.

TIP

The input size should match the size of the input address block
in RSView Machine Edition software. Similarly, the output size
of the output address block in RSView Machine Edition should
also match.