48 Configure the Terminal as a Slave Device
8. To view the tags, double-click the Controller Tags icon in the
tree.
Notice that the input, output, and status tags are specific to the
slot the 1756-DNB module resides in, which is slot 2. The inputs
and outputs mapped in RSNetWorx software now reside in:
• Local:2:I.Data array for inputs.
• Local:2:O:Data array for outputs.
9. To enable DeviceNet communications, put the DeviceNet
1756-DNB module in Run mode by setting the run mode bit in
the output command register.
Local:2:O.Command.Register.Run.
You can do this in the ladder logic or by accessing the tag
directly.
10. Download the program to the ControlLogix processor and put