Rockwell Automation DeviceNet Communications for PanelView Plus and PanelView Plus CE User Manual
Page 67
Advertising
Publication 2711P-UM004B-EN-P - March 2007
Configure the Terminal as a Scanner 67
4. Select the Input tab to verify that the 1756-DNB data is mapped
to the PanelView Plus input image file.
The DINT slave output (Scanner_Output) created in RSLinx
Enterprise software resides in the first 4 bytes of the PanelView
Plus Input table. The Input tab shows the data mapped
correctly.
5. Select the Output tab to verify that the 1756-DNB data is
mapped to the PanelView Plus output image file.
The DINT slave input (Scanner_Input) created in RSLinx
Enterprise software resides in the first 4 bytes of the PanelView