Publication 2711P-UM004B-EN-P - March 2007
Configure the Terminal as a Slave Device 43
8. Select the Output tab to verify that the PanelView Plus I/O is
mapped to the 1756-DNB output image file.
The DINT slave input (Slave_Input alias) created for the
PanelView Plus slave in RSLinx Enterprise software resides in the
first 4 bytes of the 1756-DNB output table.
9. Click OK.
You are prompted to download the changes to the 1756-DNB
module.
10. Click Yes to download the configuration.
The 1756-DNB module is now configured to scan the slave I/O
in the PanelView Plus terminal.