Configure the Terminal as a Slave Device 17
6. In the Add Device Selection dialog, select the communications
card appropriate for your terminal size and click OK.
• The correct card for the PanelView Plus 400 and 600 terminals
is 2711P-RN10C.
• The correct card for the PanelView Plus 700-1500 terminals is
2711P-RN10H.
7. Set the node address to 2, the communication rate to match the
1756-DNB DeviceNet module, and click OK.
The General tab of the DeviceNet Scanner Properties dialog
specifies the name, node address, virtual backplane slot, and
communication rate of the DeviceNet scanner. The virtual
backplane of the PanelView Plus has two slots. Because the
terminal resides in slot 0, the DeviceNet scanner is automatically
assigned to slot 1.