Publication 2711P-UM004B-EN-P - March 2007

44 Configure the Terminal as a Slave Device

Summary

The scanlists are now configured for both the 1756-DNB DeviceNet
module and the PanelView Plus terminal.

Use RSLogix 5000 Software

You must now add the DeviceNet I/O configuration in the 1756-DNB
module to the controller tags database in RSLogix 5000 software. You
can then put the 1756-DNB module in Run mode and initiate data
transfer.

For these examples, the module is in slot 0.

1. Verify that the 1756-L63 ControlLogix processor is in slot 0.

2. Open a new application.

3. Right-click the I/O Configuration icon and select New Module.

IMPORTANT

To change the scanlist for a device on the network, you must
place the device in Idle mode before downloading the changes.
On the PanelView Plus terminal, you can load the application
but not run it.