62 Configure the Terminal as a Scanner
3. Click Slave Mode button.
The Slave Mode configuration dialog appears.
4. Check the Enable Slave Mode checkbox to enable Slave mode
and edit the Slave mode configuration.
5. Under Change of State / Cyclic, set these parameters to use
Cyclic I/O messaging:
• Select Cyclic
• Input Size = 4
• Output Size = 4
The configuration will transfer 4 bytes of input data and 4 bytes
of output data using cyclic I/O messaging.
6. Click OK to save the data.
TIP
The input size should match the size of the input address block
in RSView Machine Edition. Similarly, the output size of the
output address block in RSView Machine Edition should also
match.