Rockwell Automation DeviceNet Communications for PanelView Plus and PanelView Plus CE User Manual

Page 62

Advertising
background image

Publication 2711P-UM004B-EN-P - March 2007

62 Configure the Terminal as a Scanner

3. Click Slave Mode button.

The Slave Mode configuration dialog appears.

4. Check the Enable Slave Mode checkbox to enable Slave mode

and edit the Slave mode configuration.

5. Under Change of State / Cyclic, set these parameters to use

Cyclic I/O messaging:

• Select Cyclic
• Input Size = 4
• Output Size = 4

The configuration will transfer 4 bytes of input data and 4 bytes
of output data using cyclic I/O messaging.

6. Click OK to save the data.

TIP

The input size should match the size of the input address block
in RSView Machine Edition. Similarly, the output size of the
output address block in RSView Machine Edition should also
match.

Advertising