Top of Integral Isolation Transformer Section

Figure 87 - Isolation Transformer Fan Removal

1.

Remove the top plate of the ventilation housing and label fan supply leads
before disconnecting.

2.

Remove the bolts retaining the cross channel and withdraw the fan and
channel from housing.

3.

Disassemble and replace the fan.

4.

Reassemble in the reverse order of removal.

Inlet Ring

Terminal Blocks

Mounting
Holes

Cross Channel

Fan